PVC/XLPE Insulated PVC Sheathed Control Cable XLPE insulation layer has excellent heat resistance (long-term working temperature can reach 90℃), suitable for high temperature environment; PVC sheath is corrosion-resistant and moisture-proof, suitable for various indoor and outdoor working conditions.
The rated voltage is 450/750V and below, which meets the needs of low-voltage control circuits. XLPE insulation material has low loss and high insulation resistance characteristics, which improves signal transmission stability.
Rated voltage: 450/750V
Conductor: Solid or Stranded Copper
Insulation: PVC/XLPE
Sheathing: PVC
Temperature rating: from 0ºC to +70ºC.
Typical models:KVV/KYJV
Cross-Sectional Area mm² | Thickness of Insulation mm | Thickness of Sheath mm | Overall Diameter mm | Approx Weight kg/km | Max.D.C resistance of at 20℃ Ω/km | |
min | max | |||||
2×1.5 | 0.7 | 1.2 | 7.9 | 9.5 | 92 | 12.1 |
2×2.5 | 0.8 | 1.2 | 9.0 | 10.9 | 124 | 7.41 |
2×4 | 0.8 | 1.2 | 9.9 | 11.9 | 163 | 4.61 |
2×6 | 0.8 | 1.2 | 10.8 | 13.1 | 212 | 3.08 |
3×1 | 0.6 | 1.2 | 7.4 | 8.9 | 89 | 18.1 |
3×1.5 | 0.7 | 1.2 | 8.3 | 10.0 | 114 | 12.1 |
3×2.5 | 0.8 | 1.2 | 9.5 | 11.5 | 156 | 7.41 |
3×4 | 0.8 | 1.2 | 10.5 | 12.7 | 210 | 4.61 |
3×6 | 0.8 | 1.2 | 11.5 | 13.9 | 279 | 3.08 |
4×1 | 0.6 | 1.2 | 7.9 | 9.6 | 107 | 18.1 |
4×1.5 | 0.7 | 1.2 | 9.0 | 10.9 | 139 | 12.1 |
4×2.5 | 0.8 | 1.2 | 10.4 | 12.5 | 194 | 7.41 |
4×4 | 0.8 | 1.2 | 11.4 | 13.8 | 264 | 4.61 |
4×6 | 0.8 | 1.5 | 13.2 | 15.9 | 373 | 3.08 |
5×1 | 0.6 | 1.2 | 8.6 | 10.3 | 126 | 18.1 |
5×1.5 | 0.7 | 1.2 | 9.7 | 11.7 | 65 | 12.1 |
5×2.5 | 0.8 | 1.2 | 11.3 | 13.6 | 232 | 7.41 |
5×4 | 0.8 | 1.5 | 13.0 | 15.7 | 338 | 4.61 |
5×6 | 0.8 | 1.5 | 14.3 | 17.3 | 451 | 3.08 |
... | ... | ... | ... | ... | ... | ... |
24×2.5 | 0.8 | 1.7 | 23 | 28 | 986 | 7.41 |
Industrial Control Systems: PVC/XLPE Insulated PVC Sheathed Control Cable is suitable for automation equipment, mechanical control loops and monitoring systems. It is stable in high temperature or chemical corrosion environments, especially the XLPE insulation layer can withstand higher temperatures.
Building and Infrastructure: Control Cable is used in building automation systems and lighting control loops. Its PVC sheath provides mechanical protection and adapts to indoor wiring requirements.
Energy and Power Systems: Control Cable is used as a connecting cable for low-voltage control loops in substations, power plants and other places to support signal transmission and protection functions of power equipment.